Show/Hide

 To protect the health and safety of the public during the Coronavirus (COVID-19) pandemic, City Hall and other facilities are closed to the public until April 30. The City continues to provide services during this time and recommends using technological alternatives where possible. For more information related to City services during this emergency, please visit the Coronavirus (COVID-19) page or call the City at 310-802-5000.

Certificate of Occupancy

Print
Press Enter to show all options, press Tab go to next option

Certificate of Occupancy SprinklerCertificate of Occupancy beams & sprinkler system

The following document is the check sheet utilized by Manhattan Beach Fire Department while completing TCO/ Final Certificate of Occupancy inspections.

TEMPORARY CERTIFICATE of OCCUPANCY / FINAL CERTIFICATE of OCCUPANCY

Circled items require correction before clearance will be given.

EXTERIOR

  • Address visible from the street.
  • Red curbs in front of FDC and/or hydrant(s).
  • Fire Lanes clearly marked / posted.  Proper emergency vehicle access.
  • Exterior alarm (horn/strobe) device visible from the street (minimum of 8' above grade).
  • Knox boxes in place with all required keys (access, fire alarm, etc) and information sheet
  • All keys are marked / tagged.
  • FDC caps in place and intact with no obstructions. Caps turn freely. Proper signage in place.

INTERIOR

Fire Alarm System

  • Remote annunciation panel visible and accessible.
  • A floor plan (drawing/schematic) provided adjacent to the remote panel and is clearly marked.
  • Fire alarm detection, initiating, and signaling devices visible and intact (operational).
    • Tampers
    • Smokes
    • Heat
    • Duct
    • Water Flow
    • Mag Doors  
    • Pulls
  • All required documentation properly completed and on-site with Approved as-built drawings.
  • Circuit breakers for Fire Alarm system are clearly identified and locked OPEN.

Exiting / Exit Signs / Illumination

  • Exit signs are visible and illuminated.   All signs are in working condition.
  • Emergency exit lighting units are operable and aimed properly.
  • Exiting system is clear and accessible. Clear and continuous path to the public way.
  • Stairwell doors / floor landings are properly identified.
  • Emergency Escape Plan is posted where required
  • Panic hardware installed and tested (where required)

Fire Extinguishers

  • Fire extinguishers are within proper travel distance and mounted / located so as to be visible and accessible at all times.  Extinguishers must have current CSFM tag
  • Kitchen fire extinguisher in place

Fire Extinguishing Systems

  • Fire sprinkler control valves and other system control valves clearly identified, secured in the OPEN position and accessible.  Area control drawings are visible and mounted properly.
  • Kitchen Hood extinguishing system tested / serviced / accepted.
  • Standpipe connections are clear and unobstructed.  Caps turn freely.
  • Fire sprinkler / standpipe system components are properly secured.
  • Current T-19 5-year Certificate for the sprinkler system is properly posted. 
  • There are no obstructions to the fire protection system.  Storage at least 24" below fire sprinklers.

Elevators

  • Current State certificate
  • Phone and recall function properly
  • FD control keys in Knox Box

General

  • All self-closing doors close properly and are tight fitting, with smoke gaskets in place.
  • Proper clearance in front of electrical panels (minimum of 3').
  • Proper identification on all doors required to be marked (Electrical room, Sprinkler control room, etc.)
  • All penetrations in rated walls are properly sealed.
  • Spare sprinkler heads, pull station reset equipment, and needed access keys available
  • Occupancy load displayed
  • All Fire Department Conditions of Approval satisfied. Note any items deferred.
  • Emergency contact list is current.
  • Contact and other pertinent information entered in premise history at RCC.